Ir para o conteúdo principal
CloudStudio

HVAC / Thermostats

Reporting HVAC Device Status

The HTTP integration of HVAC devices uses the following structure:

POST /services/gear/DeviceIntegrationService.svc/UpdateHVACStatus HTTP/1.1
Host: gear.cloud.studio
Content-Type: application/json

{
	"accessToken": "xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx",
	"endpointID": 1,
	"mode": 4,
	"fanMode": 1,
	"setpoint": 21,
	"ambientTemperature": 21.5,
	"timestamp": "2021-02-23T14:55:03"
}

Parameters

NameDescriptionData Type
accessTokenAccess token with permissions to update endpoint information. See this page for more information.text
endpointIDUnique endpoint identifier or combination of device address and endpoint address in format [deviceAddress]:endpointAddress (e.g.: [device-1234]:1). These values can be found on the endpoint management page.numeric
modeCurrent device mode: 1 = off; 2 = on, auto mode; 3 = on, heat mode; 4 = on, cool mode; 5 = on, dehumidify mode; 6 = on, fan mode.numeric
fanModeCurrent fan mode: 1 = auto; 2 = low speed; 3 = medium speed; 4 = high speed.numeric
setpointThe target temperature, in degrees Celsius.numeric
ambientTemperatureThe ambient temperature, in degrees Celsius.numeric
timestampOptional value indicating the UTC date and time corresponding to the measurement. The date format must match one of those specified in the date formats section. If the field is omitted, the platform will assume the measurement corresponds to the current date and time.text